Siemens 6ES7134-6PA00-0CU0 – SIMATIC ET 200SP Analog Input Module
Siemens 6ES7134-6PA00-0CU0 – SIMATIC ET 200SP Analog Input Module. Van Haelen supplies it refurbished, with a 24-month warranty.
Also written as: 6ES7 134-6PA00-0CU0, 6ES71346PA000CU0
The Siemens 6ES7134-6PA00-0CU0 is a S7-300 control component. Manufacturer type designation: SIMATIC ET 200SP Analog Input Module. When replacing, check the product version (issue) on the rating plate; for most installations the same or a higher issue is suitable. Ask us about exchange, repair and a spare-parts pool for your installation.
Available as
Product data
| Manufacturer | Siemens |
|---|
| Part number | 6ES7134-6PA00-0CU0 |
|---|
| Type designation | SIMATIC ET 200SP Analog Input Module |
|---|
| ETIM | EC001596 |
|---|
Documentation from the manufacturer
Faults and fixes 6ES7134-6PA00-0CU0
Problems with 6ES7134-6PA00-0CU0: BF LED, station unreachable
On an ET 200 interface module BF indicates a bus fault: on PROFINET a missing or wrong device name and IP setting, on PROFIBUS a wrong address or a cable without termination. After replacement the device name must be assigned again (TIA: Online, assign device name) or the PROFIBUS address switch set to the same position. SF with BF off points to a module in the station: wrong module, missing module or a channel diagnostic.
6ES7134-6PA00-0CU0: module drops out under vibration or heat
In distributed stations contact problems on the terminal or base module and overheating in the cabinet are the most common causes of sporadic drop-outs. Check the module's latch on the base module, the earth rail and the cabinet temperature. If the station keeps dropping out at the same module, replace that module.
Fault not fixed: replace, exchange or repair the 6ES7134-6PA00-0CU0?
Replacing from stock is the fastest route when a machine is down. Van Haelen supplies the 6ES7134-6PA00-0CU0 refurbished: tested to this family's test protocol, with a test report per serial number, with a 24-month warranty. The current lead time is shown with the condition on this page. Prefer an exchange: you get a refurbished unit straight away and return the faulty one within 14 days. Repairing your own unit is also possible: diagnosis, then a fixed price.
What information should I send for a quick diagnosis?
A photo of the rating plate (order number, product version, firmware), the exact fault code or LED state, when the fault occurs (at power-up, on enable, under load) and what you have already tried. For PLCs an export of the diagnostic buffer, for drives the parameter set. With that we can usually say the same day whether replacing, exchanging or repairing is best.
Frequently asked questions
What does refurbished mean?
Cleaned, inspected, aged or critical components replaced and tested to our test protocol for this product family. You get a 24-month warranty, a test report and a serial number label.
What should I check when replacing a 6ES7134-6PA00-0CU0?
Check the product version (issue) on the rating plate; for most installations the same or a higher issue is suitable.
Can I exchange or repair my faulty unit?
Yes. With an exchange Van Haelen supplies a refurbished unit straight away and you return the faulty one. With a repair you first get a diagnosis and then a fixed price, with test report and warranty.